FGWilson easYgen 3200
Presentation
The easYgen-3200 is a versatile control unit, incorporating all the features of the easYgen-2500 including enhanced load sharing, and is adaptable to every application. Typical applications include co-generation, standby, AMF, peak shaving, import / export or distributed generation. This control panel is suitable for synchronising up to 32 generator sets running in island mode, mains parallel and multiple unit mains parallel operations.Benefits
- Capable of generator set-to-set, set-to-mains and multiple set-to-mains synchronisation for up to 32 generator sets
- Enhanced system flexibility meets demanding customer specifications
- User friendly interface via 320×240 pixel graphical interactive 5.7” LCD
- Easy system navigation via programmable soft keys
- Multilingual capability: English, Chinese, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish, Turkish and Finnish
- Multiple communication protocols for communication with Engine Control Units (ECUs), external I/O boards, PLCs and modems
Features
- Power and reactive power load sharing up to 32 units including load-dependent start / stop
- Engine start / stop and generator set measuring and protection
- Automatic base loading
- Running hours balancing
- Import / export control
- Dead bus closure negotiation
- ECU monitoring and alarm management as well as remote start / stop and control commands
- PLC-like programming with Logics Manager
- 300-entry, time and date stamp log
- Operating hours / start / maintenance counters
- Configurable trip levels / delays / alarm classes
- Field configurable application settings
- Multi-level password protection
- RP3000 remote display panel available for management and control from adjacent plant room

Protection
Generator Set- Over / under voltage and frequency
- Dead bus detection
- Overload
- Unbalanced load
- Reverse / reduced power
- Time over current
- Instantaneous over current
- Measured ground fault
- Phase rotation
- Power factor
- Over / under speed
- Battery over / under voltage
- Auxiliary excitation
- Speed / frequency mismatch
- Over / under voltage and frequency
- Phase shift
- Rotation field

Inputs / Outputs (I/O)
- Two separate sets of 3-phase true r.m.s. voltage measuring inputs for the generator set and mains, and 2-phase busbar voltage
- 3-phase true r.m.s. generator set current / power
- 1-phase true r.m.s. current input freely configurable
- 1 speed input (magnetic / switching)
- 10 configurable discrete alarm inputs
- Up to 12 programmable discrete outputs
- Three configurable analogue inputs
- Two configurable analogue outputs
- Two CAN bus communication networks (up to 32 participants, isolated)
- Two serial ports supporting Modbus RTU Protocol, RS-485 and RS-232 (isolated)
Optional features
NetBiter FGW200
Remote management for new and existing generator set installations.With software designed exclusively for FG Wilson, the FGW200 offers new opportunities for remote access over the internet and mobile phone. The NetBiter unit is suitable for use in new and existing installations due to control panel Auto Detect software which offers plug and play capability.

Remote management at a new level
- Reducing the need to travel to remote sites for maintenance purposes
- Minimising downtime with instant information about equipment health
- Theft prevention through generator set tracking
- Fuel level monitoring to optimise fuel inventory
- Start up logging to help prevent generator set misuse
- Allowing multiple project and device management through NetBiter.net
Features
- New Auto Detect software allows retrofit to PowerWizard 2.1, easYgen-2500, easYgen-3200 control panels and ATI transfer panels
- Built in web interface for data monitoring
- Built in alarm manager for SMS, email and SNMP
- Built in data logger of historical trends
- GSM / GPRS modem included
- All software included, easily upgraded remotely and provided with no licensing cost
I/O Expansion Module†
Connection to and from external system devices enabling more flexibility to meet your specfic power requirements.Features
- 8 configurable discrete alarm inputs
- 8 configurable relay outputs
- Connection to easYgen control panel via CAN bus
- Input and output configuration via onboard easYgen relay manager
- Remote control of output relays via CAN bus
- The I/O Expansion Module can be used with other manufacturer’s controls. Consult Woodward product manual 37135 for information regarding the address assignments of the CAN bus interface

– Aviable through Power Solutions†
Features and Options | 1002T | DCP-10 | DCP-20 | PW 1.1 | PW 1.1+ | PW 2.1 | EG 2500 | EG 3200+ |
---|---|---|---|---|---|---|---|---|
Instrumentation | ||||||||
LCD Display with Auto Power ff | No | No | No | Yes | Yes | Yes | Yes | Yes |
Battery Trickle Charge Ammeter | No | No | No | Optional | Optional | Optional | Optional | Optional |
Audible Alarm | No | Yes | Yes | Optional | Optional | Optional | Optional | Optional |
Remote Annunciator | No | No | No | No | Optional | Optional | Optional | Optional |
AC Metering | ||||||||
Voltmeter 3-phase ( L – L & L – N ) |
Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Amps (per phase and average) |
Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Frequency | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
kW (total & per phase) |
No | No | Yes | No | No | Yes | Yes | Yes |
kVA (total & per phase) |
No | No | Yes | No | No | Yes | Yes | Yes |
kVAr (total & per phase) |
No | No | Yes | No | No | Yes | Yes | Yes |
Power Factor (overall and per phase) |
No | No | Yes | No | No | Yes | Yes | Yes |
kW Hours | No | No | Yes | No | No | Yes | Yes | Yes |
kVAr Hours | No | No | Yes | No | No | Yes | Yes | Yes |
DC Metering | ||||||||
Battery Voltmeter | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Engine Hours Run | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Engine Jacket Water Temperature (in °C or °F) |
No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Lube Oil Pressure (in Psi, kPA or bar) |
No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Engine Speed (rpm) |
No | No | Yes | Yes | Yes | Yes | Yes | Yes |
Crank Attempt Counter | No | No | No | No | Yes | Yes | Yes | Yes |
Start Counter | No | No | No | No | Yes | Yes | Yes | Yes |
Protection | 1002T | DCP-10 | DCP-20 | PW 1.1 | PW 1.1+ | PW 2.1 | EG 2500 | EG 3200+ |
---|---|---|---|---|---|---|---|---|
Fail to Start | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Low Oil Pressure | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
High Engine Temperature | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Underspeed, Overspeed | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Loss of Engine Speed Detection | No | No | No | Yes | Yes | Yes | Yes | Yes |
Low / High Battery Voltage | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Battery Charger Failure (if Battery Charger fitted) |
No | No | No | Yes | Yes | Yes | Yes | Yes |
Under Volts, Over Volts | No | Yes | Yes | Yes | No | Yes | Yes | Yes |
Under Frequency, Over Frequency | No | No | No | Yes | No | Yes | Yes | Yes |
Overcurrent | No | No | No | No | Yes | Yes | Yes | Yes |
Configurable Sender Input (for ‘Oil Temperature’ or ‘Fuel Level’ options only) |
No | No | No | Yes | No | Yes | Yes | Yes |
Earth Leakage Protection | No | No | No | Optional | Optional | Optional | Optional | Optional |
Earth Fault Protection | No | No | No | Optional | Optional | Optional | Optional | Optional |
Low Fuel Level Alarm | No | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Low Fuel Level Shutdown | No | No | No | Optional | Optional | Optional | Optional | Optional |
High Fuel Level Alarm | No | No | No | Optional | Optional | Optional | Optional | Optional |
Fuel Transfer System Control | No | Optional | Optional | No | Optional | Optional | Optional | Optional |
Low Coolant Level Shutdown | No | No | No | Optional | Optional | Optional | Optional | Optional |
Low Coolant Temperature Alarm | No | Yes | Yes | Yes | Yes | Yes | Optional | Optional |
High Lube Oil Temperature Shutdown | No | No | No | Optional | Optional | Optional | Optional | Optional |
Overload via Alarm Switch on Breaker | No | No | No | Optional | Optional | Optional | No | Optional |
Overload via Over Current Relay | No | No | No | Optional | Optional | No | No | Optional |
Low Gas Pressure | No | No | No | No | No | No | No | Optional |
High Gas Pressure | No | No | No | No | No | No | No | Optional |
High Exhaust Temperature Alarm | No | No | No | Yes | Yes | Yes | Optional | Optional |
Protection Monitoring | ||||||||
Name of Each Event | No | No | No | Yes | Yes | Yes | Yes | Yes |
Engine Hours at First Occurrence of Event | No | No | No | Yes | Yes | Yes | Yes | Yes |
Time and Date of First Occurrence of Event | No | No | No | No | No | Yes | Yes | Yes |
Engine Hours at Last Occurrence of Event | No | No | No | Yes | Yes | Yes | Yes | Yes |
Number of Occurrences of Event | No | No | No | Yes | Yes | Yes | Yes | Yes |
Spare Fault Channels | ||||||||
Number of Channels Available | 0 | 0 | 4 | 3 | 5 | 5 | 5 | 6 |
Exceptions | ||||||||
On models P730P1 – P1100E1 | No | No | No | No | 3 | 3 | 4 | 5 |
On models P1250 – P2500-1 | No | No | No | No | 2 | 2 | 3 | 4 |
Controls | 1002T | DCP-10 | DCP-20 | PW 1.1 | PW 1.1+ | PW 2.1 | EG 2500 | EG 3200+ |
---|---|---|---|---|---|---|---|---|
2 LED Status Indicators (1 red shutdown, 1 amber warning) |
No | No | Yes | Yes | Yes | Yes | Yes | Yes |
Run key, Auto Key and Stop Key with LED indicators | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Lamp Test | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Alarm Acknowledge Key | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Menu Navigation Keys | No | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Dedicated Key to reset all events | No | No | No | Yes | Yes | Yes | No | No |
Engine and AC Metering Short Cut Keys | No | No | No | Yes | Yes | Yes | No | No |
Main Menu and Event Log Short Cut Keys | No | No | No | Yes | Yes | Yes | Yes | Yes |
Control Module Keys with Tactile Feedback | No | No | No | Yes | Yes | Yes | Yes | Yes |
CAN 1 Data Link – J1939 for communicating with electronic engine control modules | No | No | No | Yes | Yes | Yes | Yes | Yes |
CAN 2 Accessory Data Link – for additional modules remote annunciator, digital input/output module | No | No | No | No | No | Yes | Yes | Yes |
Remote Monitoring and Control Data Link (ModBus) | No | No | No | No | No | Yes | Yes | Yes |
Real Time Clock | No | No | No | No | Yes | Yes | Yes | Yes |
Service Maintenance Interval Warning | No | No | No | No | No | Yes | Yes | Yes |
Remote Monitoring and Control | No | No | No | No | No | Optional | Optional | Optional |
Static Battery Charger | No | No | No | Optional | Optional | Optional | Yes | Yes |
Static Battery Charger with Auto Boost | No | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Volt Free contacts for: Common Alarm & Generator Set Running | No | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Engine Coolant Heater Controls | No | No | No | Optional | Optional | Optional | Optional | Optional |
Control Panel Heater | No | No | No | No | Optional | Optional | No | Optional |
Volts Adjust Potentiometer | No | No | No | Optional | Optional | Optional | Yes | Yes |
Speed Adjust Potentiometer | No | No | No | Optional | Optional | Optional | Yes | Yes |
Speed Adjust Switch | No | No | No | Optional | Optional | Optional | Optional | Optional |
Oil Temperature Display | No | No | No | No | Optional | Optional | Optional | Optional |
Oil Temperature Gauge | No | No | No | Optional | Optional | Optional | No | No |
Lube Oil Temeperature displayed on LCD screen | No | No | No | Optional | Optional | Optional | Optional | Optional |
Fuel Level Switch | No | Optional | No | Optional | No | No | Optional | Optional |
Fuel Level Sender & Display | No | No | Optional | No | Optional | Optional | Optional | Optional |
Panel Lockdown Stop Push Button with security key | No | No | No | Optional | Optional | Optional | No | No |
Netbiter Internet Monitoring and Control Unit | No | No | No | No | No | No | Optional | Optional |
Mains Load Sensing Unit | No | No | No | No | No | No | No | Optional |
Additional 8 inputs and 8 outputs | No | No | No | No | No | No | No | Optional |